Applications
The RCD is in conformity with the standards of IEC61008, GB16916 and BS EN61008. The RCD can cut off the fault circuit immediately on the occasion of shock hazard or earth leakage of trunk Thus it is suitable to avoid the shock hazard and fire caused by earth leakage.
The RCD is mainly suitable for use in variety of plants and enterprises, building constructions, commerce, guesthouses and families, It can be used in circuits up to single phase 230/240V, three phase 400/415V 50 to 60Hz. RCD is not suitable for use on DC pulse system.
Availability: | |
---|---|
America
Specification | |
Standard | IEC61008, GB16916, BSEN61008 |
RatedVoltage(Un ) | 2pole:230/240VAC,4pole:400/415VAC |
Rated Curent (ln) | 25,32,40,63A |
Rated residual operating current(1△n) | 30,100,300,500mA |
Rated residual non-operation current(I△no) | 0.5l△n |
Residual current off-time | ≤0.1s |
Minimum value of rated making and breaking capacity (lm) | In=25,40A Inc=1500A; In=63A Inc=3000A |
Rated conditional short-circuit current (lnc) | 6000A |
Endurance | ≥4000 |