The Main Function&Characteristics
1 HMM3EL applies 32 digit ARM CPU.In real time,it can handle signals and realize itelligent control,
2.This device has friendly interface through LCD,and easy to operate.
3.Hesidual current.(earth leakage).prolection,with residual current adjustable,and can be reclosed.
Availability: | |
---|---|
America
1.In feal time,it can monitor and trace the residual current,adjust steps:automatically,to guarantee the product operation rate and relbility,
2.Long time delay,short time delay and instaneous time protection,it applies electronic tip,and has no concerns with power voltage.
3.tt owrns high breaking capacity.to guarantee the flbility at short circuit protection in lies.
4.t owns protection of over voltage,under voltage,phase loss;
5.In real time 1o display the rsidual current,three phase power voltage.and load current:
6.The protection function and parameter can be setup and moditled online.
7.Trlp types(resldual current,lock,overload,under voltage,over voltage.phase Ioss),recognize,display,and can be restored,check and deleted;
8.Network tpe owns communication function,it can realize remotely communication,measure,control,and adjust.
Auto Reclose
While the resi dual current exceeds action current value gear and trip, the device will auto reclose after 20-60 seconds, while manually reclose is not imited. The device reclosed for 5 seconds and the circuit taulty disappeared. it reclose successtully, and the breeker runs nomally; Otherwise. the device will trip and lock itl circult tauly not removed, The device won’ t aulo feclose and requires manually operation to teclose.
Over voltage Protection
While the line voltage is higher than the setup protection value, the breaker will trip. While the line voltage recovers to normal, the breaker will auto reclose and run. The voltage satup value range is. 250-300V. normally, setup 280V while manufacture. The customer can set up or clase this protecton as needed.
Under vltage Potectin
While the line vllage is lower than the setup protection value,the breaker will trip.While the line vllage recovers to normal,the breaker will auto reclose and run.The vltage setup value range is 150-200V.normally setup 170V while manufacture,The customer can set up or close this protection a8 needed.
Phase Loss Protection
While the line terminal has phase loss, the breaker will trip. The breaker will auto reclose and run while the phase loss clrcult faulty disappears.
Interink Communication Protection
This device may connect with other fire extinguishing equipment and owns protection as below.
Product Type and Function
Product Type and Function | intelligent | Network | |
Protection Function | Overload | ● | ● |
Short Circuit | ● | ● | |
Residuai Current | ● | ● | |
Auto Reclose | ● | ● | |
Phase Loss | ● | ● | |
Ovor Voltage | ● | ● | |
Under Voltago | ● | ● | |
Measurement and Display | Residual Current Auto Test | ● | ● |
Three phase voltago | ● | ● | |
Three phase current | ● | ● | |
Characteristics Setup | Rated Residual Current | ● | ● |
Overload Time Deiay | ● | ● | |
Short Circuit Time Deiay | ● | ● | |
Instaneous Short.Circuit | ● | ● | |
Over voltage Value | ● | ● | |
Under voltage Value | ● | ● | |
Time.Date | ● | ● | |
Protection in&Out | ● | ● | |
Info Restore.Chack and display | Residual Current Trip | ● | ● |
RS-485 | ● | ● | |
Conmmunication | DLT645 | ● | ● |
Main Technical Parameter
Specification &Type | HWM3EL-125CY | HWM3EL-250CY | HWM3EL-400CY | HWM3EL-800CY |
Case.Curgnt | 125 | 250 | 400 | 800 |
Poles | 3P+N | 3P+N.2P | 3P+N | 3P+N |
Rated voltage Ue(V) | AC400/50HZ | AC400/50HZ | ||
Rated InsulationVoltage Ui(V) | AC1000V | AC1000V | ||
RatedInsulation VoltageUimp(V) | 8000 | 8000 | ||
Arc Distance(mm) | ≧50 | ≧100 | ||
Rated short circuit breaking capacity(icn) | 50 | 65 | ||
Operatyion short circuit breaking capaciyu(ics) | 35 | 42 | ||
Rated Residual short circuit (break)capacityiam(ka) | 12.5 | 20 |
Residual Current Trip Characteristics | AC type | AC type | |||
Rated Residual Trip Current 1Δn(mA) | 50/100/200/400/800/800MCU Auto trace or manual setup | 100/200/300/500/800/1000 Auto trace or manual setup | |||
Residual Trip Time Characteristics | Time Deiay/Non Time Deiay | ||||
Time Delay Limit Un-Drive Time | 0.06/0.1/0.2 Select:21an 0.06/0.1/0.2可选:2lan | ||||
Breaking Time | lAn≤0.5:2lAn≤0.2;5IAn≤0.15 | ||||
Auto Reclose Time(s) | 20-60 | ||||
Operation Characleriscs 【times】 | Power On | 1500 | 1000 | 1000 | 1000 |
Power Off | 8500 | 70000 | 4000 | 4000 | |
ToralTip | 10000 | 8000 | 5000 | 5000 | |
Overload.Short circuit Characteristics | Three steps protection,electronic adjust,see more on”Protection Characteristics Instruction” | ||||
Over Voltage Value | Setup Value (250-300)±5% | ||||
Under Voltage Value | Setup Value (150-200)±5% | ||||
Connect Control Time (ms) | ≤40ms | ||||
Communication Deiay Time(ms) | ≤200ms |
Overload Long Time Delay Parameter Setup
Parameter | Case Current | Setup Value | Adjust Value while manufacture |
Action Setup ValueIr1 | 125A | 40A、50、63A、80A、100A、125A | 125A |
250A | 100A、125A、140A、160A、180A、200A、225A、250A | 250A | |
400A | 200A、225A、250A、315A、350A、400A | 400A | |
800A | 400A、500A、630A、700A、800A | 800A | |
Time Delay Setup Value TI | 3s,4s,6s,8s,10,12s,16s,18s,OFF | 12S |
Instantaneous Action Characteristics
Charactoristics | Current Times | Trip Time | Time delay tolerance |
No action characteristics | ≤0.85 | No action | |
Action characteristics | >1.15 | Instantaneous Action | ±40ms |
Residual Current Protection Characteristics
Parameter | Setup Value | Setup Value while Manufacture |
Residual Action Current 1Δn | 100,200,300,500,800,1000,Automatic | 500 |
Protection Action Characteristics
Parameter | Characteristics | |||
Raled No Action Current | 0.5 1Δn | |||
Rated Action Current | ≥0.75 1Δn | |||
Time delay characteristics | 2lan Limit No Drive Time(At) | Breaking Time | ||
1Δn | 2 1Δn | 5 1Δn | ||
No Time Delay | ≤0.3s | ≤0.15s | ≤0.04s | |
0.06 | ≤0.5s | ≤0.2s | ≤0.15s | |
0.1 | ≤1s | ≤0.4s | ≤0.20s | |
0.2 | ≤1.5s | ≤0.6s | ≤0.30s |
The variant value on each different gear while auto gear mode
Gear Value(mA) | Variant(mA) |
100 | 50 |
200 | 100 |
300 | 150 |
500 | 250 |
600 | 300 |
800 | 400 |
1000 | - |
Protection Action Characteristics
Environment Temperture | Current Name | Adjust Current Times | Agreed Time |
+40℃ | Agreed not-trip Current | 1.05tr | 2h |
Agreed trip current | 1.3tr | 2h |
Time Delay Characteristics
Overioad Protection Anti-time limit :
T=(6rt/l)2 time delay accuracy: ± 10%, of which T is action time value, Ir 1 is long time protection setup value.
l is faulty current. tL is long time delay setup value.
Short Time Delay Protection for Short Circuit
Short Time Delay Protection for Short Circuit is to protect and avoid the resistant short circuit in distribution system, time delay trip is to realize the selection protection.
The parameter setup to short time delay protection for short circuit.
The parameter setup | Setup Value | The adjust value while manufacture |
Short time delay action current setup value lr2 | 2r1.2.5r1.3lr1.4r1.5lr1. | 6ir1 |
Short ime delay setup value ts | 0.18,0.2s,0.38,0.48,0.66,0.8s,1.0%,OFF | 0.4s |
The Action Characteristics for short time delay of Short Circuit
Characteristics | Timos of faulty current | Trip Time | Time Delay Tolerance |
No action characteristics | ≤0.9lr2 | No Action | ±40ms |
No action characteristics | >1.15lr2 | Time Delay Action | ±40ms |
Instantaneous Parameter
Parameter Setup | Setup Value | Adjusted Value while manufacture |
Instantaneous Action Current Setup Value ir3 | 4lr1,6lr1,71r1,8lr1,10lr1,11lr1,12lr1,13lr1,14lr1,OFF | 10lr1 |
Note:The circuit will be open if long time short connected.
1.In feal time,it can monitor and trace the residual current,adjust steps:automatically,to guarantee the product operation rate and relbility,
2.Long time delay,short time delay and instaneous time protection,it applies electronic tip,and has no concerns with power voltage.
3.tt owrns high breaking capacity.to guarantee the flbility at short circuit protection in lies.
4.t owns protection of over voltage,under voltage,phase loss;
5.In real time 1o display the rsidual current,three phase power voltage.and load current:
6.The protection function and parameter can be setup and moditled online.
7.Trlp types(resldual current,lock,overload,under voltage,over voltage.phase Ioss),recognize,display,and can be restored,check and deleted;
8.Network tpe owns communication function,it can realize remotely communication,measure,control,and adjust.
Auto Reclose
While the resi dual current exceeds action current value gear and trip, the device will auto reclose after 20-60 seconds, while manually reclose is not imited. The device reclosed for 5 seconds and the circuit taulty disappeared. it reclose successtully, and the breeker runs nomally; Otherwise. the device will trip and lock itl circult tauly not removed, The device won’ t aulo feclose and requires manually operation to teclose.
Over voltage Protection
While the line voltage is higher than the setup protection value, the breaker will trip. While the line voltage recovers to normal, the breaker will auto reclose and run. The voltage satup value range is. 250-300V. normally, setup 280V while manufacture. The customer can set up or clase this protecton as needed.
Under vltage Potectin
While the line vllage is lower than the setup protection value,the breaker will trip.While the line vllage recovers to normal,the breaker will auto reclose and run.The vltage setup value range is 150-200V.normally setup 170V while manufacture,The customer can set up or close this protection a8 needed.
Phase Loss Protection
While the line terminal has phase loss, the breaker will trip. The breaker will auto reclose and run while the phase loss clrcult faulty disappears.
Interink Communication Protection
This device may connect with other fire extinguishing equipment and owns protection as below.
Product Type and Function
Product Type and Function | intelligent | Network | |
Protection Function | Overload | ● | ● |
Short Circuit | ● | ● | |
Residuai Current | ● | ● | |
Auto Reclose | ● | ● | |
Phase Loss | ● | ● | |
Ovor Voltage | ● | ● | |
Under Voltago | ● | ● | |
Measurement and Display | Residual Current Auto Test | ● | ● |
Three phase voltago | ● | ● | |
Three phase current | ● | ● | |
Characteristics Setup | Rated Residual Current | ● | ● |
Overload Time Deiay | ● | ● | |
Short Circuit Time Deiay | ● | ● | |
Instaneous Short.Circuit | ● | ● | |
Over voltage Value | ● | ● | |
Under voltage Value | ● | ● | |
Time.Date | ● | ● | |
Protection in&Out | ● | ● | |
Info Restore.Chack and display | Residual Current Trip | ● | ● |
RS-485 | ● | ● | |
Conmmunication | DLT645 | ● | ● |
Main Technical Parameter
Specification &Type | HWM3EL-125CY | HWM3EL-250CY | HWM3EL-400CY | HWM3EL-800CY |
Case.Curgnt | 125 | 250 | 400 | 800 |
Poles | 3P+N | 3P+N.2P | 3P+N | 3P+N |
Rated voltage Ue(V) | AC400/50HZ | AC400/50HZ | ||
Rated InsulationVoltage Ui(V) | AC1000V | AC1000V | ||
RatedInsulation VoltageUimp(V) | 8000 | 8000 | ||
Arc Distance(mm) | ≧50 | ≧100 | ||
Rated short circuit breaking capacity(icn) | 50 | 65 | ||
Operatyion short circuit breaking capaciyu(ics) | 35 | 42 | ||
Rated Residual short circuit (break)capacityiam(ka) | 12.5 | 20 |
Residual Current Trip Characteristics | AC type | AC type | |||
Rated Residual Trip Current 1Δn(mA) | 50/100/200/400/800/800MCU Auto trace or manual setup | 100/200/300/500/800/1000 Auto trace or manual setup | |||
Residual Trip Time Characteristics | Time Deiay/Non Time Deiay | ||||
Time Delay Limit Un-Drive Time | 0.06/0.1/0.2 Select:21an 0.06/0.1/0.2可选:2lan | ||||
Breaking Time | lAn≤0.5:2lAn≤0.2;5IAn≤0.15 | ||||
Auto Reclose Time(s) | 20-60 | ||||
Operation Characleriscs 【times】 | Power On | 1500 | 1000 | 1000 | 1000 |
Power Off | 8500 | 70000 | 4000 | 4000 | |
ToralTip | 10000 | 8000 | 5000 | 5000 | |
Overload.Short circuit Characteristics | Three steps protection,electronic adjust,see more on”Protection Characteristics Instruction” | ||||
Over Voltage Value | Setup Value (250-300)±5% | ||||
Under Voltage Value | Setup Value (150-200)±5% | ||||
Connect Control Time (ms) | ≤40ms | ||||
Communication Deiay Time(ms) | ≤200ms |
Overload Long Time Delay Parameter Setup
Parameter | Case Current | Setup Value | Adjust Value while manufacture |
Action Setup ValueIr1 | 125A | 40A、50、63A、80A、100A、125A | 125A |
250A | 100A、125A、140A、160A、180A、200A、225A、250A | 250A | |
400A | 200A、225A、250A、315A、350A、400A | 400A | |
800A | 400A、500A、630A、700A、800A | 800A | |
Time Delay Setup Value TI | 3s,4s,6s,8s,10,12s,16s,18s,OFF | 12S |
Instantaneous Action Characteristics
Charactoristics | Current Times | Trip Time | Time delay tolerance |
No action characteristics | ≤0.85 | No action | |
Action characteristics | >1.15 | Instantaneous Action | ±40ms |
Residual Current Protection Characteristics
Parameter | Setup Value | Setup Value while Manufacture |
Residual Action Current 1Δn | 100,200,300,500,800,1000,Automatic | 500 |
Protection Action Characteristics
Parameter | Characteristics | |||
Raled No Action Current | 0.5 1Δn | |||
Rated Action Current | ≥0.75 1Δn | |||
Time delay characteristics | 2lan Limit No Drive Time(At) | Breaking Time | ||
1Δn | 2 1Δn | 5 1Δn | ||
No Time Delay | ≤0.3s | ≤0.15s | ≤0.04s | |
0.06 | ≤0.5s | ≤0.2s | ≤0.15s | |
0.1 | ≤1s | ≤0.4s | ≤0.20s | |
0.2 | ≤1.5s | ≤0.6s | ≤0.30s |
The variant value on each different gear while auto gear mode
Gear Value(mA) | Variant(mA) |
100 | 50 |
200 | 100 |
300 | 150 |
500 | 250 |
600 | 300 |
800 | 400 |
1000 | - |
Protection Action Characteristics
Environment Temperture | Current Name | Adjust Current Times | Agreed Time |
+40℃ | Agreed not-trip Current | 1.05tr | 2h |
Agreed trip current | 1.3tr | 2h |
Time Delay Characteristics
Overioad Protection Anti-time limit :
T=(6rt/l)2 time delay accuracy: ± 10%, of which T is action time value, Ir 1 is long time protection setup value.
l is faulty current. tL is long time delay setup value.
Short Time Delay Protection for Short Circuit
Short Time Delay Protection for Short Circuit is to protect and avoid the resistant short circuit in distribution system, time delay trip is to realize the selection protection.
The parameter setup to short time delay protection for short circuit.
The parameter setup | Setup Value | The adjust value while manufacture |
Short time delay action current setup value lr2 | 2r1.2.5r1.3lr1.4r1.5lr1. | 6ir1 |
Short ime delay setup value ts | 0.18,0.2s,0.38,0.48,0.66,0.8s,1.0%,OFF | 0.4s |
The Action Characteristics for short time delay of Short Circuit
Characteristics | Timos of faulty current | Trip Time | Time Delay Tolerance |
No action characteristics | ≤0.9lr2 | No Action | ±40ms |
No action characteristics | >1.15lr2 | Time Delay Action | ±40ms |
Instantaneous Parameter
Parameter Setup | Setup Value | Adjusted Value while manufacture |
Instantaneous Action Current Setup Value ir3 | 4lr1,6lr1,71r1,8lr1,10lr1,11lr1,12lr1,13lr1,14lr1,OFF | 10lr1 |
Note:The circuit will be open if long time short connected.