| Availability: | |
|---|---|
HWQ1-80SE
YUANKY
America
The complete model coding system defines core configuration parameters of HWQ1‑80SE series automatic transfer switches, every segment corresponds to electrical specification and structural feature of the unit:
Rated working control voltage: AC220V, AC110V optional
Rated working current selection: 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A
Pole number selection: 2‑Pole (2P), 3‑Pole (3P), 4‑Pole (4P) to match single‑phase and three‑phase power systems
Product structural type: MA Two‑Stage ATS
Installation form: DIN‑rail mounting
Product category: PC‑Grade Automatic Transfer Switch (ATS)
As a genuine PC‑class automatic transfer switch, HWQ1‑80SE adopts integrated main circuit switching architecture, rather than assembling discrete contactors for power switching. The two‑stage working structure implements automatic logic judgment and switching between main power supply and standby power supply. It eliminates extra matching work of peripheral auxiliary components, lowers system matching error risks, and improves the overall reliability of dual‑power supply loops. The 4‑pole variant provides complete neutral‑pole disconnection function, which is essential for TT and TN‑S earthing systems with strict neutral‑line safety requirements.
Specification Item | Parameter Value |
|---|---|
Rated Operational Current | 32A, 40A, 50A, 63A, 80A |
Rated Insulation Voltage | 690V |
Rated Control Operating Voltage | AC220V |
Automatic Transfer Switching Time | 20ms |
Mechanical Endurance Life | >6000 operating cycles |
Electrical Endurance Life | ≥1500 operating cycles |
The 20‑millisecond ultra‑fast transfer time is a core advantage of this series. Upon detection of main‑source failure, the mechanism completes circuit disconnection from faulty source and connection to backup source within merely 20ms. Such short switching gap greatly reduces the risk of sensitive loads shutting down, suitable for inductive loads, capacitive loads and mixed general‑type loads.
High endurance figures verify long‑term operational stability. More than 6000 mechanical cycles guarantee repeated mechanical movement performance of internal driving and contact mechanism; no less than 1500 electrical cycles ensures contacts can bear frequent on‑off of load current without rapid ablation, fitting working conditions with frequent power source switching. Rated insulation voltage reaches 690V, granting ample voltage safety margin for low‑voltage distribution networks, adapting to fluctuation of on‑site grid voltage.
This is a slim compact ATS specially optimized for cabinet space‑saving. Engineering drawings demonstrate the terminal layout and overall outline dimension for the 4P version. All power input and output terminals are arranged on the front face of the housing. Front‑accessible terminals allow installers to finish wiring without removing the device from DIN rail, facilitating assembly, field inspection and later circuit modification.
Installation Specification Details
Mounting method: Standard 35 mm DIN‑rail clip‑on installation. Users only need to hook the upper buckle onto the DIN rail and press down the bottom latch for firm fixation. Removal can be done by prying the bottom spring buckle, no extra screw fixing brackets are needed, greatly shortening on‑site installation hours.
Terminal wiring compatible wire cross‑section area: 1 ~ 25 mm², covering multi‑strand flexible cables and solid copper wires for different current grades.
Wiring screw model: M5 hexagon screw. The recommended tightening torque is strictly 2.5 N·m.
Torque guidance matters significantly: insufficient torque will result in loose connection, contact overheating and potential fire hazard; over‑tightening may crack terminal base or damage screw thread. Installers should use calibrated torque screwdrivers for wiring operations.
The slim housing cuts down depth and width occupation inside distribution cabinets. Multiple units can be arranged side‑by‑side on one DIN rail, maximizing utilization of limited cabinet inner space. The mechanical structure is fully enclosed, which can block large‑particle dust from directly invading contact components under normal indoor environment.
Ultra‑Fast Automatic Power Source Transfer 20 ms transfer response realizes near‑uninterrupted power supply for downstream loads. Once main power appears power loss, undervoltage or phase loss fault, internal control circuit will trigger mechanical action immediately to switch load to standby power source. It effectively safeguards sensitive equipment including PLC controllers, monitoring systems, communication equipment and precision lighting systems against unexpected power interruption.
PC‑Grade Integrated ATS Architecture Different from CB‑grade ATS solutions built by circuit breakers or contactor combinations, this PC‑grade HWQ1‑80SE adopts dedicated switching main body. The mechanical interlock structure physically prohibits simultaneous closing of main‑power and standby‑power loops, eliminating catastrophic risk of two power sources short‑circuiting. The built‑in interlock avoids complex external interlock wiring and human operation mis‑fault.
Space‑Saving Slim Compact Design with Flexible Configuration The slim‑form factor targets modern compact distribution box and small‑size control cabinet applications. It provides 2P, 3P, 4P pole options. 2P for ordinary single‑phase dual‑power circuits; 3P for three‑phase three‑wire systems; 4P for three‑phase four‑wire systems requiring neutral line breaking. Rich rated current options ranging up to 80A cover loads from small control loops to medium‑power terminal power supply circuits.
Superior Mechanical & Electrical Service Life Mechanism is tested to survive over 6000 mechanical cycles and minimum 1500 electrical operation cycles. High‑quality alloy contact material resists electric arc ablation. It can sustain frequent switching actions in environments where mains power is unstable and backup power often engages, lowering frequency of component replacement and reducing overall system maintenance cost.
Simple Installation & User‑Friendly Wiring Layout DIN‑rail clip‑on mounting supports rapid assembly and disassembly. Front‑side terminals make wiring visible and easy to check. Markings on housing clearly identify main power source, standby power source and load terminals, helping technicians prevent wrong wiring during on‑site construction.
HWQ1‑80SE PC‑grade two‑stage slim ATS serves as critical dual‑power switching core for various places that demand power continuity:
Commercial buildings: Shopping malls, office buildings, hotel emergency lighting, elevator auxiliary power supply, fire‑fighting related power loops
Industrial sites: Factory control cabinets, automation production line auxiliary power, on‑site monitoring equipment power supply
Public infrastructure: Communication base station power distribution, traffic signal equipment, community public power distribution boxes
Civil and special projects: Data terminal equipment, security monitoring systems, small‑scale backup power distribution systems
It is suitable for applications where the main power is municipal grid and standby power can be generator set or another independent grid source.
Pre‑operation safety check: Before power‑on commissioning, verify wiring correctness strictly according to wiring instruction. Confirm that each M5 terminal screw is tightened to 2.5 N·m torque, and wire cross‑section falls within 1‑25 mm² matching range. Confirm no stray wire scraps remain inside the unit housing to prevent short‑circuit risk.
Storage requirement: When the product is not put into use immediately, store it in dry, ventilated, dust‑free warehouse environment, avoid humidity, corrosive gas and direct sunlight.
Periodic maintenance items: During long‑term running, conduct regular visual inspection. Check for terminal overheating signs, loose screws, dust accumulation on device surface. For systems with high switching frequency, inspect mechanical action status regularly. Cut off both main and standby power supply completely before any inspection or maintenance work to avoid electric shock hazard.
Warning: Only qualified electricians who are familiar with low‑voltage power distribution standards are allowed to perform installation, wiring and maintenance work for this ATS device.