| Availability: | |
|---|---|
Yuanky
America
序号 |
Item |
品 |
Data |
|||
1 |
额定电压 Rated voltage |
KV |
40.5 |
|||
2 |
额定电流 Rated Current |
A |
||||
3 |
额定短路开断电流 Rated short circuit breaking current |
KA |
20 |
25 |
||
4 |
额定短路关合电流(峰值) Rated short-circuit current(peak) |
50 |
63 |
|||
5 |
额定短时耐受(热稳定)电流 Rated short(thermal stable)current |
20 |
25 |
|||
6 |
额定峰值耐受(动稳定)电流 Rated peak withstand(dynamic stable)current |
50 |
63 |
|||
7 |
额定短路持续时间 Rated short circuit duration |
S |
4 |
|||
8 |
额定绝缘 水平 Rated insulation level(1min) |
工频耐受电压 1min power frequancy withstand voltage |
干式 Dry |
KV |
95 |
|
湿式 Wet |
80 |
|||||
雷电冲击耐压(峰值) Lightning impulse withstand voitage(peak) |
185 |
|||||
9 |
额定操作顺序 Rated operating sequence |
次 Times |
20 |
|||
10 |
额定短路开断电流开断次数 Rated short-circuit current breaking times |
ms |
≤80 |
|||
11 |
全开断时间(配弹簧操动机构) Full-off time(with spring operating mechanism) |
分-0.3S-CO- 180S-CO 0-0.3S-CO-180S-CO |
||||
12 |
机械寿命 Mechanical life |
10000 |
||||
13 |
额定操作电压 Rated operating voltage |
AC110,220,DC110,220 |
||||
14 |
触头开距 Contact opening distance |
20 |
||||
15 |
触头超程 Contact over-travelling distance |
5±1 |
||||
16 |
弹跳时间 Bounce time |
≤5 |
||||
17 |
每相回路直流电阻 DC resistance per phase circuit |
≤120 |
||||
18 |
断路器外形尺寸(长X宽X高) Circuit Breaker Dimensions(LxWxH) |
2460×2400×500 |
||||
19 |
断路器带机构总质量 Total Weight With Mechanism |
kg |
1100 |
|||